Features:

  • universal input for PT 100, thermo couple, mA, V
  • inputs selectable via software modi
  • freely adjustable control and display area
  • self-optimization of the PID control parameters
  • input for external given value
  • 2 internally given values switchable via keys or binary input
  • 2 (URE 422) relay outputs for control or limit values
  • analog output with galvanic separation for the control variable Y, the given value W or the actual value X (option)
  • outputs switchable via software modi for steady, two-point, three-point or three-point step action 




Technical Data

Universal controller URE 422

Display/ indicators:
3 ½-digit digital display for the actual value and parameters 
3 ½-digit digital display for the setpoint and function play

2 (4) singlel LED indicators for the relay output
3 singlel LED indicatirs for the control deviation

Push buttons:
Manual/ Atumatic switchover for Y Changeover switch for switching from internal to external setpoint

Analogue input:
Adjustable filter (0..99,9 s) 1st order in the input Universal input switchable via software modes for für mA, V, PT 100 oder thermocouple NiCr-Ni, PtRh-Pt, Fe-CuNi, Cu-CuNi, lambda probe.
Freely selctable control or display range within the specified limits 
Setpoint can be freely limitd 
Zero shift Xo
Switchover Winternal to Wexternal

Binary inputs:
BE1 for external switchover Win-tern /Wextern
BE1 for selection of the 2 internal setpoints WI1/WI2

Controller function:
Fixed setpoint controller
Master controller 
Follower controller
PID finction freely selectable (slef-optimisation)
Integral limitation on start-up



Relay outputs:
Output function via software modes
Relay output BA1: Two-step output or limit contac at X, XW, W oder Y
Relay output BA2: 
Two-step output or limit contact at X, XW, W oder Y
Relay output BA3 and BA4:
Limit contact at X, XW, W or Y
Relay output BA1 + BA2: three-step output, three-step stepping output without feedback or with feedback
Relay contacts solderable as make- or-break contact, breaking capacity
230 V, 3 A, 690 VA

Typ URE 422 RA:
Adjustable minimum and maximum limitation for output Y
0(4) ... 20 mA, load max. 500 Ω
or 0(2) ... 10 V, load min. 1 kΩ

Typ URE 422 R-SP-AC
Additional supply power to connected pyrometers 24 V DC, 60 mA

Input:
0(4) ... 20 mA, Ri > 50 Ω
0(2) ... 10 V or mV
Ti > 100 KΩ

Thermocouples:
NiCr-Ni 0..1300 °C Typ K
PtRh-Pt 0..1700 °C Typ S
Fe-CuNi 0..900 °C Typ L
Cu-CuNi 0..600 °C Typ U
The control range can be freely set via the software function E min. for the zero point an dE max. for the upper range value

Temperature compensation:
via a  PT 100 at the connection terminals





 Resistant thermometer PT 100:
Measuring range switchable, and zero point and upper range value can be freely selected within the range.
Measure ranges:
0 ... 199,9 °C
0 ... 600 °C

-100 ... +150 °C
-100 ... +500 °C 

Resolution:
11 Bit (2048 increments)
Controller error: 0.1 % (mA, V)
0.2 % (PT 100), 0.3 % (thermocouple) 
Ambient temperautre influence: 0.05 %/ 10 k


Measuring circuit monitoring for discontinuity:
Configurable 
Yb= -100 ... 100 %

Wextern:
0(4) ... 20 mA, Ri > 50 Ω
0(2) ... 10 V,    Ri > 100 KΩ

Digital interface:
RS 232 C, without galvanic isolation 
RS 485 GT, with galvanic isolation 
Baudrate: 4800 or 9600 Baud

Housing
Installation via front plate
96 x 96 mm 
installation depth 125 mm (front plate fitting 91 x 91 mm)
Prtoection front IP 65

Power supply
100 ... 240 V AC, 48 ... 62 Hz 
oder 24 V DC
Power consumption 8 VA


Ambient operating temperature:
- 10 ... +50 °C

Measure cycle:
10 ms
 

 

Downloads:

Electronics

Universal controller URE 422

 
The universal controller URE 422 are designed for steady and switched actuators. The main field of application are drive and control technologies for process engineering, laboratory, testing, climate and environmental technology, the machine and kiln construction in the chemicals, food and glass industry.