Often contact measurements with thermocouples with ceramic sheaths are still used to monitor the crown temperature during the glass melting process.
However, rapid ageing and limited service life require periodic accuracy checks with portable pyrometers. Thermocouples with platinum sheaths are used for molten glass in the tank and feeder. More and more, thermocouples are being replaced by wear-free pyrometers.
To avoid damage to the product, only a non-contact temperature measurement method can be employed to monitor the temperature in glass forming.
Both portable and stationary pyrometers can bring about large rationalisation effects.
This is especially true
- when starting up and running glass production lines
- when changing over to a different line of products
- for quality control of manufactured products
- when manufacturing glass laboratory equipment such as test tubes and beakers
- when conducting industrial research for the flat glass, container glass or household glass sectors
- for subsequent finishing and processing of glass products, such as ampoules and glass-to-metal bonds
Typical measuring points
In the glass industry, the locations for pyrometer temperature measurements can be categorised according their thermal radiation characteristics:
- Black bodies are measured by pyrometers which "see" though a small eyehole into a uniformly heated cavity (fuel-heated melting tanks). A thermocouple with a protection tube can be installed at the crown or at the side wall of the tank furnace, or the pyrometer can "look" into a closed ceramic annealing tube.
- Opaque emitters or grey bodies. In this case, the pyrometer is aimed at metallic surfaces, e.g. at the open inside of moulds. The thermal energy is only emitted from the mould surface.
- Transparent radiation sources where the thermal radiation is emitted from the surface and from deeper glass layers as well. The depth at which the pyrometer can detect the radiation depends on the spectral absorption coefficient of the hot glass and the pyrometer’s spectral range.
Ultimately, one must distinguish between temperature measurements with continuous or discontinuous signal sequences (temperature of gobs, moulds and products). Discontinuous measurements require pyrometers with small response times and a peak picker.
Glass as a transparent volume radiating source
When measuring black or grey bodies, the primary criteria for selecting a pyrometer are temperature range, target spot diameter, measuring distance and response time. For transparent glass applications, the thickness of the glass and the pyrometer’s measuring depth must also be considered. This depends on the pyrometer’s spectral range and the spectral absorption coefficient of the particular type of glass and of the glass temperature.
Glass as a grey body


ρ (λ, Τ) + α (λ, Τ) + τ (λ, Τ) = 1 (1)
If a glass medium, due to its thickness, is opaque for certain parts of the IR radiation, in other words, if the transmissivity is negligibly low (τ < 0.01), then the following equation based on Kirchhoff’s law of thermal radiation will be true for emissivity ε:
ε (λ, Τ) = 1 - ρ (λ, Τ) (2)
In these cases, the measured glass object is a grey body. The spectral development of reflectivity as per equation (2) generally indicates emissivity as a function of wavelength λ.
Fig. 1 shows the measured spectral reflectivity ρ (λ) for borosilicate glass1) and the spectral emissivity ε (λ) as calculated using equation (2) as a function of wavelength, taking into account the negligibly low transmissivity τ (λ) < 0.01.
In addition, the chart shows some spectral ranges of pyrometers, each sensitive to the appropriate emissivity setting ε (λ) for borosilicate glass.
One can see that wavelengths between 0.5 and 7.8 µm exhibit a nearly constant emissivity between 0.95 and 0.96.
For the spectral range 8 – 14 µm an average emissivity value ε = 0.91 should be selected.
Unlike metal surfaces where the spectral emissivity decreases with increasing wavelengths or is fluctuating or varies in relation to temperature and time, clear glass surfaces with negligible transmissivity in the spectral range from 0.5 to 7.8 µm may be regarded as grey bodies. The clear glass surface is not subject to perceptible changes as it is, for example, the case with metal surfaces undergoing oxidation.
1) Borosilicate glass 3.3 (ISO-3585) can be used for laboratory instruments under high thermal stress, electron and x-ray tubes, for pipings and technical plants.
Temperature measurements independent of the glass thickness
From the law of absorption
I = IO e -[α (λ, Τ) · X] (3)
follows at approximately full absorption
I/IO = 0.01 = e -[α (λ, Τ) · X99] (4)
the relation for the product of the exponent
α (λ, Τ) · X99 = 4.6 (5)
resp. after conversion
X99 = 4.6 ÷ α (λ, Τ) (6)
α (λ, Τ) here is the spectral absorption coefficient of the measured glass at the specific glass temperature while X99 defines the glass thickness at which 99 % of the radiation IO from the depth X99 is absorbed in the glass on its way to the glass surface.
This characteristic value X99 is called measuring depth of the pyrometer. Just as the absorption coefficient, the measuring depth is a function of the wavelength λ and the glass temperature T.
The measuring depth X99 characterises the thickness of the glass layer from which, starting at the glass surface down to the measuring depth X99, a total of 99% of the radiation is emitted and the pyrometer creates a signal.
For the calculation of the spectral measuring depth X99, glass with homogeneous temperature distribution was assumed. In the wavelength range 0.5 to 2.0 µm which is the range of free transmission for uncoloured glass, the measuring depth X99 will be between 90 to 400 mm, depending on temperature.
At wavelengths >2.0 µm, these temperature gradients will decrease at longer wavelengths.
When a pyrometer with Si sensors (0.8 – 1.1 μm) is employed, the measuring depth X99 for glass temperatures is approximately
• 90 mm at 600 °C (the glass will appear dark red)
• 170 mm at 1000 °C
• 300 mm at 1200 °C
Pyrometers with a InGaAs sensor (1.1 – 1.7 μm) will measure at a somewhat greater measuring depth than pyrometers with Si sensor.
Pyrometers with a spectral range of 4.6 to 4.9 µm have a measuring depth X99 of a maximum of 0.7 mm.
Pyrometers with a spectral range >8 µm will only reach X99 at a depth of 0.04 mm. These devices capture merely the surface temperature and react on effects of convection.
Fig. 3 shows the large differences in the spectral measuring depth X99 of sheet glass and green glass in the spectral range 0.5 to 3 µm at glass temperatures of 20, 1250 and 1300 °C.
While the measuring depth of sheet glass at 1300 °C more or less equals that of borosilicate glass, the measuring depth of green glass, due to its larger absorption coefficient, is only 6 mm at a temperature of 20 °C and 12 mm at 1250 °C.
This means that even pyrometers with Si sensors cannot "see" very deep into green glass. As a rule, glass objects are non-transparent at wavelengths >4 µm, thus at this spectral range, the shallow measuring depth X99 for borosilicate glass as shown in fig. 2, will also apply to sheet glass and green glass.
The pyrometer detects 50% of the energy from the glass surface and from layers below the surface down to a depth which is commensurate to one sixth of the measuring depth X99. When the temperature distribution is inhomogeneous (surface glass is hotter than layers below the surface), these 50% will be even shallower (indicated by the dot-dash line).
Selecting a pyrometer according to glass thickness
In order to obtain a representative signal for the glass temperature, one must employ a spectral pyrometer where the maximum measuring depth is smaller than the glass thickness at the measuring point.
If the glass thickness is less than the pyrometer’s measuring depth, the pyrometer will more or less “see” through the glass object and pick up radiant energy from the background. Variations in the glass thickness will distort the signal, for example when a single channel spectral pyrometer with Si sensor is aimed horizontally through a gob.
Nonetheless, an accurate temperature reading can be obtained if the pyrometer is aimed diagonally at the gob of molten glass as it is dispensed from the gob feeder or a two-colour pyrometer with Si sensor can be employed.
If, however, the measuring depth is substantially smaller than the glass thickness, the pyrometer will predominantly pick up thermal energy at the uppermost glass layers just below the surface which might be subject to strong convection currents. The reading obtained then mainly represents surface disturbances. Therefore, a pyrometer which measures close to the surface (4.6 to 4.82 µm) at a measuring depth of 0.7 mm at the workcell of a ball gatherer with a glass height of approximately 800 mm is not suitable.
The control loop of an electric overhead heater, for example, is extremely sensitive to this external interference. The heater will shut off when the gathering ball, coated with molten glass, enters the gathering bay, and turn on again when the ball gatherer is withdrawn. This will produce misleading temperature data.
This source of error can be eliminated by a pyrometer with Si sensor with a measuring depth of approx. 300 mm. Even when tilted at an angle of 30°, this pyrometer will “see’’ 150 mm into the glass target.
When buying a pyrometer, always make sure to select a pyrometer whose measuring depth X99 is less than the glass thickness, always considering the highest possible value for the measuring depth for the type of glass measured. This will prevent the sensor from “looking through’’ the glass at any temperature which would result in a glass thickness related measuring error.
Two-channel/two-colour pyrometers
Two-colour pyrometers should be employed when the thickness of the measured glass is less than the maximum depth X99, but greater than one sixth of that value. At that thickness, both channels will still receive 50 % of the thermal radiation (Fig. 4). The two-colour pyrometer will determine the true temperature value, because signal attenuation will be the same at both wavelengths (numerator and denominator) and the quotient will remain constant.
Table 1 lists various pyrometers with their respective spectral and temperature ranges and shows the depth X99 for different kinds of glass and some typical applications for spectral and two-colour pyrometers.
Pyrometer types and typical applications in the glass industry
Stationary pyrometers
Spectral pyrometers with Si or InGaAs sensors are especially suitable for measuring glass temperatures at the melting tank, in workcells and feeder, due to their large measuring depth for colourless glass and their temperature ranges from 250 °C to 3000 °C.
The CellaTemp PA 20 / 30 with sighting aid or the CellaTemp PK 21 / 31 without sighting aid is preferable for measuring glass temperatures at workcells of the ball gatherer. From a safe distance, this pyrometer “sees” through the orifice into the glass melt (Fig. 5). This pyrometer features a peak picker function to smooth any sporadic signal fluctuations caused by the movement of the gathering ball in the pyrometer’s optical path.
Ceramic sighting tubes and air purging devices serve to keep the pyrometer optics clean and help extend maintenance intervals. For inspection purposes, the sensor head can be easily disconnected in seconds without the use of tools.
With green glass, spectral pyrometers with Si sensor can measure at a maximum depth of 12 mm. Thus the CellaTemp PA30 with through-the-lens-sighting or integrated video camera can be employed for measuring green glass gob temperatures when the gob diameter is >15 mm. The peak picker function can compensate for signal interruptions during gob cutting.
The spectral pyrometers CellaTemp PA 20/21 with InGaAs sensors can measure deeper into colourless glass and green glass than pyrometers with Si sensors.
However, since the surface characteristics of the mould will vary over time from shiny to dull as well as before and after each lubrication, their surface emissivity will fluctuate greatly. To eliminate these emissivity fluctuations, a cavity should be drilled into the outside of the mould into which the pyrometer can be aimed.
When the cavity’s drill depth is at least six times the diameter, the pyrometer will “see’’ into what can be considered a grey body with an emissivity of 0.95.
In this way, regardless of the cast iron mould's inner surface condition, a stationary pyrometer can obtain a reproducible and representative temperature value for the mould.
The CellaTemp PA 21 or CellaTemp PKF 26 with optical fibre cable and optical sensor head is ideal to measure mould temperatures. The small sensor head can be mounted to a convenient location near the press or the press-and-blow machine. The spot light feature illuminates the target spot and indicates the exact spot diameter in true size. The pyrometer is then adjusted to the “measuring cavity” (Fig. 7).
The two-colour pyrometers CellaTemp PA40 / 41 / 43, CellaTemp PK 63 / 68 and CellaTemp PKF 66 with measuring ranges from 450 – 3000 °C can be employed in the following situations:
- The glass thickness D at the measured spot is less than the pyrometer’s measuring depth X99 for glass but more than one sixth of that value, therefore is 1/6 · X99 < D < X99
- When it is required to measure inductively heated metal parts that will be sealed into the rear side of the glass and it is for technological reasons only possible to measure through thick and often tinted glass.
The panorama pyrometers CellaTemp PA 43 and CellaTemp PK 63 have a rectangular measurement area. This facilitates the alignment on the gob considerably. As long as the gob remains within the rectangular measurement area, the pyrometer provides a correct reading.
With a gob diameter of 30 – 40 mm, the pyrometer should be aimed towards the gob at an angle of 30° from the horizontal position to “enlarge” the glass thickness.
The signal interruptions during periodic gob cutting are compensated for by the integrated peak picker.
Due to the low measuring depth of X99 <0.7, the pyrometers CellaTemp PA 15 and CellaTemp PK 41/42 with a wavelength from 4.6 to 4.9 µm and ranges from 300-2500 °C measure glass surface temperatures or the mixed temperature of a near-surface glass layer. They are especially suitable for temperature monitoring of relatively thin-walled objects (glass thickness > 1 mm) of flat glass, container glass or household glassware products in processing and cooling areas.
All technological-related temperature changes are verifiable when measuring the “onion” temperature at Danner mandrels.
When measuring the tip of a blowpipe, the pyrometer signal is a representative magnitude for the temperature condition of the glass surface and the muffle chamber. The peak picker of the pyrometer eliminates the signal variations that appear periodically in function of the speed of the blowpipe.
Due to the low measuring depth of X99 < 0.04 mm, the pyrometers CellaTemp PA 10 and CellaTemp PK 11 with a wavelength of 8 – 14 µm and a range from 0 – 1000 °C measure only the surface temperature of glass (glass skin temperature). They are therefore used for thin-walled glass (thickness > 0.1 mm).
The stationary pyrometers of the PA series are characterised by their focusable optics or, optionally, through-the-lens sighting or a colour video camera. The marked target, as seen through the viewfinder or on the monitor, indicates the true size of the spot measured.
This feature facilitates pyrometer alignment, particularly when measuring small objects or when looking through narrow openings.
In addition, the measuring range of the PA pyrometers can be adjusted both at the instrument itself as well as via a standard USB or RS 485 interface, allowing for an optimal adaptation to the measuring point from the control room.
The instruments of the compact PK pyrometer series are merely 30 mm in diameter and are thus ideal when working in confined areas. Housed in an IP 65 stainless steel enclosure they can be employed in extremely harsh industrial conditions.
The measured temperature can be read on the display directly on site. All parameters and functions can be configured by keys on the instrument.
All KELLER pyrometers work with sensors receiving unmodulated radiation, i.e. the devices operate without mechanical moving parts and are maintenance-free and have a long service life.
The range of stationary pyrometers is enhanced by a comprehensive selection of mounting fittings and accessories.
Portable pyrometers
The portable pyrometers correspond to the stationary instruments in terms of temperature and wavelength range. These handhelds are suitable for temperature measuring tasks at spots where comparable stationary pyrometers are used.
The mobile devices of the CellaPort PT series are also used for temperature verification in the crown or in the upper section of melting tanks. Temperature deviations of thermocouples due to ageing, depending upon operating conditions (installation mode, temperature, energy carrier, protective tube and glass type) can easily be checked with these portable pyrometers.
The CellaPort PT series are characterised by the following features:
- Parallax-free and true-to-side through-the-lens sighting with diopter correction and extended pupil distance
- Reflex optics with very large field of view and precise target marking to visualize the exact measuring area
- Premium quality focusable optics with precise lenses for high optical resolution
- 10 models to match with a large number of applications
- ATD function for automatic detection of objects
- Spectral pyrometers and two-colour pyrometers
- Robust aluminium housing
- Patented traffic light function (SSI – Signal Strength Indicator) in the view finder indicates the correct distance to the target and sufficient signal strength
- Optionally as panorama pyrometer® with a rectangular measurement area
Even with a low number of cuts, it can be used for mobile gob temperature measurements when aimed diagonally at the gob as it is dispensed from the gob feeder.
The CellaPort PT 110 (0 - 1000 °C) allows measurements of moulds, conveyor belts and glassware before entering and after leaving the lehr; therefore it is an important tool for the plant operator.
The CellaPort PT 140/143 is a portable two-colour pyrometer that supplies reliable measurement readings even in a very dusty and steamy environment or when gob diameters are very small. The CellaPort PT 143 has a rectangular measurement area. This greatly facilitates "looking" at the target object from a large distance.
Conclusion
- Described were special features of pyrometric temperature measurements at the transparent radiation source glass and presented were both stationary and portable pyrometers for temperature measurements of glass in melting tanks, workcells and feeders and for the measurement of gobs, moulds and glass articles.
- The selection of a single channel pyrometer is based on the condition "maximum measuring depth X99 of the pyrometer < glass thickness at the measuring site".
- A two-colour pyrometer should fulfil the condition "1/6 of the maximum visibility depth X99 of the pyrometer < glass thickness at the measuring site < maximum measuring depth X99".
- Unlike thermocouples, pyrometers are not subject to an ageing process and have a long service life.
- Pyrometers require a certain degree of maintenance to cool the optical system and to keep it clean.